-- MIB file for PoE Ethernet Sensors (PoE-X), created 4-May-2020 by KSL
-- REVISED 

POEXMIB DEFINITIONS ::= BEGIN

IMPORTS
		enterprises
        FROM RFC1155-SMI
		OBJECT-TYPE
        FROM RFC-1212
		TRAP-TYPE
        FROM RFC-1215
		DisplayString
        FROM RFC1213-MIB
		TEXTUAL-CONVENTION
	 	FROM SNMPv2-TC;

manufacturer			OBJECT IDENTIFIER ::= { enterprises 41542 }

POEX					OBJECT IDENTIFIER ::= { manufacturer 3 }
-- DESCRIPTION
--    "PoE-X Sensor platform supporting the delivery of data from a varity
--    of sensor type family on an Ethernet connection through the SNMP v1 
--    protocol and others." 

POEXGatewaySpecificInfo OBJECT IDENTIFIER ::= { POEX 1 }
-- DESCRIPTION
--    "The POEX reports certain information specific to the particular
--    gateway device, which are reported under this hierarchy."

--
-- Gateway-specific section
--

POEXGatewayID OBJECT-TYPE
    SYNTAX        Unsigned32
    ACCESS        read-only
    STATUS        mandatory
    DESCRIPTION
				"The serial number identifier of the gateway device assigned and
				programmed by the manufacturer. This will ordinarily be printed
				on a label on the housing of the device."
    ::= {POEXGatewaySpecificInfo 1}

POEXGatewayFirmwareVerNo OBJECT-TYPE
    SYNTAX        OCTET STRING
    ACCESS        read-only
    STATUS        mandatory
    DESCRIPTION
        "The version number of the firmware of the gateway device. Note that
        this can change upon a firmware update."
    ::= {POEXGatewaySpecificInfo 2}

POEXGatewaySensorDeviceCount OBJECT-TYPE
    SYNTAX        INTEGER(0..256)
    ACCESS        read-only
    STATUS        mandatory
    DESCRIPTION
        "The number of sensors registered to the gateway, i.e. on its netlist.
        Note that this can change as sensors are added or removed."
    ::= {POEXGatewaySpecificInfo 3}

POEXGatewayTrapIPAddr OBJECT-TYPE
    SYNTAX        IpAddress
    ACCESS        read-only
    STATUS        mandatory
    DESCRIPTION
        "The configured destination IP address for trap messages from this
        gateway."
    ::= {POEXGatewaySpecificInfo 4}

POEXGatewaySensorTrapPort OBJECT-TYPE
    SYNTAX        INTEGER(0..65535)
    ACCESS        read-only
    STATUS        mandatory
    DESCRIPTION
        "The configured IP port for trap messages from this gateway."
    ::= {POEXGatewaySpecificInfo 5}

--
-- Definitions of sensor-specific informational types
--

POEXSensorID ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The serial number identifier of the sensor device assigned and
				programmed by the manufacturer. This will ordinarily be printed
				on a label on the housing of the device."
		SYNTAX				Unsigned32

POEXSensorRegistrationIndex ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The index number of a sensor device in a gateway's sensor
				registration list. This is determined by the order in which a set
				of sensors has been registered, but will not change so long as
				the list remains fixed. This is included for legacy applications:
				please consider using the more convenient
				POEXSensorInfoTranslatedFormat and
				POEXSensorInfoBySensorID hierarchies."
		SYNTAX				INTEGER(0..255)

POEXDatumNo ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The datum number of a sequence of data readings from a sensor. The
				range of this type depends upon the number of datums reported by
				a sensor device. Thus, a 3-axis accelerometer sensor might report
				three datums for the X, Y and Z axes, and the datums would range
				from 1 to 3. For a simple temperature sensor reporting one
				reading, this value would always be 1."
		SYNTAX				INTEGER(1..8)

POEXSensorDeviceType ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The textual description of the type of the sensor device."
		SYNTAX				OCTET STRING

POEXDatumNumber ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The number of a datum in a set of datums comprising a sensor reading.
				For sensors reporting one datum, this will always be one. Otherwise
				it will be a number between 1 and the number of datums reported by
				the particular type of sensor."
		SYNTAX				INTEGER

POEXSensorDeviceReadingTranslatedValue ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The value of a sensor reading, in textual format, translated
				according to sensor and datum types. These formats can include
				integers, fixed-point, and binary values. In several examples:
				a pulse counter might report '12345', a current sensor might report
				'1.43', and a door closed sensor might report 'Yes'."
		SYNTAX				OCTET STRING

POEXSensorDeviceReadingTranslatedUnits ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The units or scale of value of a sensor reading, reported in textual
				format. In several examples: a pulse counter might report 'Count',
				a current sensor might report 'A', and a door sensor might report
				'Closed'."
		SYNTAX				OCTET STRING

POEXSensorDeviceReadingValuesAll ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"All of the datums for the most recent reading of the sensor device,
				separated by commas, in textual format. For example, a report for a
				temperature and humidity sensor might read '20.3, 35' indicating
				20.3 degrees at 35 percent humidity. If only one datum is reported
				by a sensor device, e.g. for a simple temperature sensor, it will be
				reported singly with no commas."
		SYNTAX				OCTET STRING

POEXSensorDeviceReadingUnitsAll ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"All of the units corresponding to the datums for the most recent
				reading of the sensor device, separated by commas, in textual
				format. For example, for a sensor reporting temperature and
				humidity this might read 'degrees C, %RH'"
		SYNTAX				OCTET STRING

POEXSensorDeviceReadingUntranslated ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The untranslated data block received from a sensor, in hexadecimal
				format. This may be used where a translating function isn't yet
				present, and for development purposes. Most users should use the
				translated values delivered in the format of
				POEXSensorDeviceReadingValuesAll."
		SYNTAX				OCTET STRING

POEXSensorDeviceReadingU32Value ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"Either a single sensor value of up to 32 bits, or half of a
				64-bit value. Thus where a sensor value is reportable in a
				single Unsigned32, one OID is sufficient to gather that value.
				Where more than 32 bits are needed, the value is reported in two
				successive values of type POEXSensorDeviceReadingU32Value.
				Where a set of datums is reported, those datums are reported
				beginning with the lowest-numbered OID proceeding sequentially
				through the highest. Thus were a sensor to report a single-bit
				value A followed by 32-bit and a 64 bit ones B and C, and where
				OIDS x.10 through x.17 were used for reporting values, the value A
				would be encoded in x.10, B in x.11 and C in x.12 (low-order bits)
				and x.13 (high-order bits). These values are merely converted
				from sensor-specific internal formats to integers, and not beyond
				to human-readable formats.
				Furthermore, where for a sensor datums extend only part-way through
				the available U32Value OIDs, the ones unused may be filled with 0.
				Where an SNMP walk is performed, the gateway may not traverse these
				unused OIDs."
		SYNTAX				Unsigned32

POEXSensorDeviceReadingAge ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The age of the sensor report received most recently from a sensor.
				That time is reported as the number of seconds between the time of
				the sensor report and the time this information is requested."
		SYNTAX				Unsigned32

POEXSensorDeviceReadingAlarming ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"Either 'Alarming' or 'Not alarming'. A device will report an alarm
				if it is programmed with a threshold found to be exceeded. Examples:
				a temperature sensor for a refrigeration unit can be programmed to
				alarm if the measured temperature rises above a threshold, and
				a door sensor might alarm if a security door is opened."
		SYNTAX				OCTET STRING

--
-- Sensor-specific section, translated format
--

POEXSensorInfoTranslatedFormatTable OBJECT-TYPE
		SYNTAX				SEQUENCE OF POEXSensorInfoTranslatedFormatEntry
		ACCESS    		not-accessible
		STATUS        mandatory
		DESCRIPTION
				"The (conceptual) table containing sensor-specific information in an
 				easy-to-use translated string format, indexed by sensor ID is reported
 				under this hierarchy. Sensor data is translated by the gateway from
 				sensor-internal format to human-readable and scriptable values. Use of
 				this format is preferred for most users. The gateway will report the
 				most current information received from sensors, according to their
 				programmed reporting period or heartbeat. When using this section
 				through getRequests or getNextRequests, successive polling is required
 				to keep sensor data current. This table can change as sensors are
 				added or removed. If queried, this OID will return the number of rows
 				in the table, which is the number of sensors registered to this gateway."
		::= { POEX 2 }

-- Table portion consisting of non-datum-specific info

POEXSensorInfoTranslatedFormatEntry OBJECT-TYPE
		SYNTAX				POEXSensorInfoTranslatedFormatEntry
		ACCESS    		not-accessible
		STATUS        mandatory
		DESCRIPTION
				"An entry (conceptual row) in the Translated Format Table containing
				the latest sensor state for a single sensor."
		INDEX   { POEXSensorInfoTranslatedFormatSensorDeviceID }
		::= { POEXSensorInfoTranslatedFormatTable 1 }

POEXSensorInfoTranslatedFormatEntry ::= SEQUENCE {
		POEXSensorInfoTranslatedFormatSensorDeviceID POEXSensorID,
		POEXSensorInfoTranslatedFormatSensorDeviceType POEXSensorDeviceType,
		POEXSensorInfoTranslatedFormatSensorDeviceReadingValuesAll POEXSensorDeviceReadingValuesAll,
		POEXSensorInfoTranslatedFormatSensorDeviceReadingUnitsAll POEXSensorDeviceReadingUnitsAll,
		POEXSensorInfoTranslatedFormatSensorDeviceRptUT POEXSensorDeviceReadingUntranslated,
		POEXSensorInfoTranslatedFormatSensorDeviceReadingTime DisplayString,
		POEXSensorInfoTranslatedFormatSensorDeviceReadingAge POEXSensorDeviceReadingAge,
		POEXSensorInfoTranslatedFormatSensorDeviceTypeNo DisplayString,
		POEXSensorInfoTranslatedFormatSensorDeviceRFStrength DisplayString,
		POEXSensorInfoTranslatedFormatSensorDeviceActive DisplayString,
		POEXSensorInfoTranslatedFormatSensorDeviceAlarming POEXSensorDeviceReadingAlarming,
		POEXSensorInfoTranslatedFormatSensorDeviceVoltage DisplayString,
		POEXSensorInfoTranslatedFormatSensorDeviceWDIndexNo DisplayString
}

POEXSensorInfoTranslatedFormatSensorDeviceID OBJECT-TYPE
    SYNTAX        POEXSensorID
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The serial number identifier of the sensor device assigned and
				programmed by the manufacturer. This will ordinarily be printed
				on a label on the housing of the device."
		::= { POEXSensorInfoTranslatedFormatEntry 1 }

POEXSensorInfoTranslatedFormatSensorDeviceType OBJECT-TYPE
    SYNTAX        POEXSensorDeviceType
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The textual description of the type of the sensor device."
		::= {POEXSensorInfoTranslatedFormatEntry 2 }

POEXSensorInfoTranslatedFormatSensorDeviceReadingValuesAll OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingValuesAll
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"All of the datums for the most recent reading of the sensor device,
				separated by commas, in textual format. For example, a report for a
				temperature and humidity sensor might read '20.3, 35' indicating
				20.3 degrees at 35 percent humidity. If only one datum is reported
				by a sensor device, e.g. for a simple temperature sensor, it will be
				reported singly with no commas. The use of this OID is recommended
				for most users, rather than the single value ones, because all values
				can be retrieved atomically from a sensor in one SNMP request."
		::= {POEXSensorInfoTranslatedFormatEntry 3 }

POEXSensorInfoTranslatedFormatSensorDeviceReadingUnitsAll OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingUnitsAll
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"All of the units corresponding to the datums for the most recent
				reading of the sensor device, separated by commas, in textual
				format. For example, for a sensor reporting temperature and
				humidity this might read 'degrees C, %RH'"
		::= {POEXSensorInfoTranslatedFormatEntry 4 }

POEXSensorInfoTranslatedFormatSensorDeviceRptUT OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingUntranslated
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The untranslated data block received from a sensor, in hexadecimal
				format. This may be used where a translating function isn't yet
				present, and for development purposes. Most users should use the
				translated values delivered in the format of
				POEXSensorDeviceReadingValuesAll."
		::= {POEXSensorInfoTranslatedFormatEntry 5 }

POEXSensorInfoTranslatedFormatSensorDeviceReadingTime OBJECT-TYPE
    SYNTAX        DisplayString
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The time of the sensor report received most recently from a sensor.
				That time is reported as the number of seconds elapsed since the epoch
				of the gateway, which is presently Jan. 1, 2010."
		::= {POEXSensorInfoTranslatedFormatEntry 6 }

POEXSensorInfoTranslatedFormatSensorDeviceReadingAge OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingAge
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The age of the sensor report received most recently from a sensor.
				That time is reported as the number of seconds between the time of
				the sensor report and the time this information is requested."
		::= {POEXSensorInfoTranslatedFormatEntry 7 }

POEXSensorInfoTranslatedFormatSensorDeviceTypeNo OBJECT-TYPE
    SYNTAX        DisplayString
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The manufacturer's type number that identifies the kind of sensor."
		::= {POEXSensorInfoTranslatedFormatEntry 8 }

POEXSensorInfoTranslatedFormatSensorDeviceRFStrength OBJECT-TYPE
    SYNTAX        DisplayString
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The signal strength, in percent, of the radio link between the gateway
				and the particular sensor, as measured at the time of the most recent
				sensor report."
		::= {POEXSensorInfoTranslatedFormatEntry 9 }

POEXSensorInfoTranslatedFormatSensorDeviceActive OBJECT-TYPE
    SYNTAX        DisplayString
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"Either 'Active' or '' (an empty string). A sensor will be reported
				active if it has recently communicated with the gateway since the last
				reboot. If a sensor device does not show active, it is likely because
				(1) the sensor lacks a power source, (2) the sensor is not in
				proximity to the gateway, or (3) the gateway has recently been
				powered on, and the sensor hasn't yet communicated."
		::= {POEXSensorInfoTranslatedFormatEntry 10 }

POEXSensorInfoTranslatedFormatSensorDeviceAlarming OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingAlarming
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"Either 'Alarming' or 'Not alarming'. A device will report an alarm
				if it is programmed with a threshold found to be exceeded. Examples:
				a temperature sensor for a refrigeration unit can be programmed to
				alarm if the measured temperature rises above a threshold, and
				a door sensor might alarm if a security door is opened."
		::= {POEXSensorInfoTranslatedFormatEntry 11 }

POEXSensorInfoTranslatedFormatSensorDeviceVoltage OBJECT-TYPE
    SYNTAX        DisplayString
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The value of the voltage of the supply powering a sensor device.
				Ordinarily this will report the voltage at the battery terminals of
				a sensor. It is provided mainly so batteries can be changed when
				depleted."
		::= {POEXSensorInfoTranslatedFormatEntry 12 }

POEXSensorInfoTranslatedFormatSensorDeviceWDIndexNo OBJECT-TYPE
    SYNTAX        DisplayString
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The index number of the sensor in the gateway's sensor registration
				table. This is the number used in referencing the sensor in the
				POEXSensorInformationBySensorRegisOrder
				hierarchy."
		::= {POEXSensorInfoTranslatedFormatEntry 13 }

-- Table portion consisting of datum-specific info (single values and units addressed by device ID and datum)

POEXSensorInfoTranslatedFormatByDatumNumberEntry OBJECT-TYPE
		SYNTAX				POEXSensorInfoTranslatedFormatByDatumNumberEntry
		ACCESS    		not-accessible
		STATUS        mandatory
		DESCRIPTION
				"An entry (conceptual row) in the Translated Format Table containing
				the sensor datums, indexed by a sensor ID and datum number."
		INDEX   { POEXSensorInfoTranslatedFormatSensorDeviceID,
							POEXSensorInfoTranslatedFormatByDatumNumberDatumNumber }
		::= { POEXSensorInfoTranslatedFormatTable 2 }

POEXSensorInfoTranslatedFormatByDatumNumberEntry ::= SEQUENCE {
		POEXSensorInfoTranslatedFormatByDatumNumberSensorDeviceID POEXSensorID,
		POEXSensorInfoTranslatedFormatByDatumNumberDatumNumber POEXDatumNumber,
		POEXSensorInfoTranslatedFormatByDatumNumberReadingValue POEXSensorDeviceReadingTranslatedValue,
		POEXSensorInfoTranslatedFormatByDatumNumberReadingUnits POEXSensorDeviceReadingTranslatedUnits
}

POEXSensorInfoTranslatedFormatByDatumNumberSensorDeviceID OBJECT-TYPE
    SYNTAX        POEXSensorID
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"The serial number identifier of the sensor device assigned and
				programmed by the manufacturer. This will ordinarily be printed
				on a label on the housing of the device."
		::= { POEXSensorInfoTranslatedFormatByDatumNumberEntry 1 }

POEXSensorInfoTranslatedFormatByDatumNumberDatumNumber OBJECT-TYPE
		SYNTAX        POEXDatumNumber
   	ACCESS    		read-only
   	STATUS        mandatory
   	DESCRIPTION
				"The number of a datum in a set of datums comprising a sensor reading.
				For sensors reporting one datum, this will always be one. Otherwise
				it will be a number between 1 and the number of datums reported by
				the particular type of sensor."
		::= { POEXSensorInfoTranslatedFormatByDatumNumberEntry 2 }

POEXSensorInfoTranslatedFormatByDatumNumberReadingValue OBJECT-TYPE
		SYNTAX        POEXSensorDeviceReadingTranslatedValue
   	ACCESS    		read-only
   	STATUS        mandatory
   	DESCRIPTION
				"The value of a sensor reading, in textual format, translated
 				according to sensor and datum types. These formats can include
				integers, fixed-point, and binary values. In several examples:
				a pulse counter might report '12345', a current sensor might report
				'1.43', and a door sensor might report 'closed'."
		::= { POEXSensorInfoTranslatedFormatByDatumNumberEntry 3 }

POEXSensorInfoTranslatedFormatByDatumNumberReadingUnits OBJECT-TYPE
		SYNTAX        POEXSensorDeviceReadingTranslatedUnits
   	ACCESS    		read-only
   	STATUS        mandatory
   	DESCRIPTION
				"The units or scale of value of a sensor reading, reported in textual
				format. In several examples: a pulse counter might report 'Count',
				a current sensor might report 'A', and a door sensor might report
				'Closed'."
		::= { POEXSensorInfoTranslatedFormatByDatumNumberEntry 4 }

--
-- Sensor-specific section, untranslated legacy format, by sensor ID
--

POEXSensorInfoBySensorIDTable OBJECT-TYPE
		SYNTAX				SEQUENCE OF POEXSensorInfoBySensorIDSensorEntry
		ACCESS    		not-accessible
		STATUS        mandatory
		DESCRIPTION
				"The (conceptual) table containing sensor information in a legacy
 				untranslated numeric format, addressed by sensor ID. This is provided
 				for users who need a precise match of the format of the older EGW1
 				platform. The gateway will report the most current information received
 				from sensors, according to their programmed reporting period or
 				heartbeat. A more convenient format to new users is available under
				the POEXSensorInfoTranslatedFormat. If queried, this
				OID will return the number of rows in the table, which is the number
				of sensors registered to this gateway."
		::= { POEX 3 }

POEXSensorInfoBySensorIDEntry OBJECT-TYPE
		SYNTAX				POEXSensorInfoBySensorIDEntry
		ACCESS    		not-accessible
		STATUS        mandatory
		DESCRIPTION
				"An entry (conceptual row) in the untranslated by-sensor-ID-order
 				table containing the latest sensor state for a single sensor."
		INDEX   { POEXSensorInfoBySensorIDSensorDeviceID }
		::= { POEXSensorInfoBySensorIDTable 1 }

POEXSensorInfoBySensorIDEntry ::= SEQUENCE {
		POEXSensorInfoBySensorIDSensorDeviceID Unsigned32,
		POEXSensorInfoBySensorIDSensorDeviceWDIndexNo INTEGER,
		POEXSensorInfoBySensorIDSensorDeviceTypeNo INTEGER,
		POEXSensorInfoBySensorIDSensorDeviceReadingAge Unsigned32,
		POEXSensorInfoBySensorIDSensorDeviceActive INTEGER,
		POEXSensorInfoBySensorIDSensorDeviceAlarming INTEGER,
		POEXSensorInfoBySensorIDSensorDeviceVoltage INTEGER,
		POEXSensorInfoBySensorIDSensorDeviceRFStrength INTEGER,
		POEXSensorInfoBySensorIDSensorDeviceRptUT DisplayString,
		POEXSensorInfoBySensorIDSensorDeviceReadingValue1 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorIDSensorDeviceReadingValue2 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorIDSensorDeviceReadingValue3 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorIDSensorDeviceReadingValue4 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorIDSensorDeviceReadingValue5 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorIDSensorDeviceReadingValue6 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorIDSensorDeviceReadingValue7 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorIDSensorDeviceReadingValue8 POEXSensorDeviceReadingU32Value
}

POEXSensorInfoBySensorIDSensorDeviceID OBJECT-TYPE
     SYNTAX				Unsigned32
     ACCESS    		read-only
     STATUS       mandatory
     DESCRIPTION
 				"The serial number identifier of the sensor device assigned and
 				programmed by the manufacturer. This will ordinarily be printed
 				on a label on the housing of the device."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 1 }

POEXSensorInfoBySensorIDSensorDeviceWDIndexNo OBJECT-TYPE
    SYNTAX				INTEGER(0..255)
    ACCESS    		read-only
    STATUS       mandatory
    DESCRIPTION
 				"The index number of the sensor in the gateway's sensor registration
 				table. This is the number used in referencing the sensor in the
 				POEXSensorInfoBySensorRegisOrder
 				hierarchy."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 2 }

POEXSensorInfoBySensorIDSensorDeviceTypeNo OBJECT-TYPE
     SYNTAX       INTEGER(1..65535)
     ACCESS    		read-only
     STATUS       mandatory
     DESCRIPTION
 				"The manufacturer's type number that identifies the kind of sensor."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 3 }

POEXSensorInfoBySensorIDSensorDeviceReadingAge OBJECT-TYPE
     SYNTAX       Unsigned32
     ACCESS    		read-only
     STATUS       mandatory
     DESCRIPTION
 				"The age of the sensor report received most recently from a sensor.
 				That time is reported as the number of seconds between the time of
 				the sensor report and the time this information is requested."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 4 }

POEXSensorInfoBySensorIDSensorDeviceActive OBJECT-TYPE
     SYNTAX       INTEGER(0..1)
     ACCESS    		read-only
     STATUS       mandatory
     DESCRIPTION
 				"Either 1 (active) or 0 (inactive). A sensor will be reported active
				if it has recently communicated with the gateway since the last
 				reboot. If a sensor device does not show active, it is likely because
 				(1) the sensor lacks a power source, (2) the sensor is not in
 				proximity to the gateway, or (3) the gateway has recently been
 				powered on, and the sensor hasn't yet communicated."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 5 }

POEXSensorInfoBySensorIDSensorDeviceAlarming OBJECT-TYPE
		 SYNTAX       INTEGER(0..1)
     ACCESS    		read-only
     STATUS       mandatory
     DESCRIPTION
 				"Either 1 (alarming) or 0 (not alarming)'. A device will report an
				alarm if it is programmed with a threshold found to be exceeded.
				Examples: a temperature sensor for a refrigeration unit can be
				programmed to alarm if the measured temperature rises above a
				threshold, and a door sensor might alarm if a security door is opened."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 6 }

POEXSensorInfoBySensorIDSensorDeviceVoltage OBJECT-TYPE
		SYNTAX        INTEGER(0..255)
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
				"A value representing the voltage of the supply powering a sensor
				device. Ordinarily this will report the voltage at the battery
				terminals of a sensor. It is provided mainly so batteries can be
				changed when depleted. The formula for calculating the voltage from
				this number is: voltage=(150 + v) / 10.0."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 7 }

POEXSensorInfoBySensorIDSensorDeviceRFStrength OBJECT-TYPE
     SYNTAX       INTEGER(-128..127)
     ACCESS    		read-only
     STATUS       mandatory
     DESCRIPTION
 				"The signal strength, in percent, of the radio link between the gateway
 				and the particular sensor, as measured at the time of the most recent
 				sensor report."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 8 }

POEXSensorInfoBySensorIDSensorDeviceRptUT OBJECT-TYPE
     SYNTAX       DisplayString
     ACCESS    		read-only
     STATUS       mandatory
     DESCRIPTION
 				"The untranslated data block received from a sensor, in hexadecimal
 				format. This may be used where a translating function isn't yet
 				present, and for development purposes. Most users should use the
				translated values delivered in the format of
				POEXSensorDeviceReadingValuesAll."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 9 }

POEXSensorInfoBySensorIDSensorDeviceReadingValue1 OBJECT-TYPE
    SYNTAX		POEXSensorDeviceReadingU32Value
    ACCESS		read-only
    STATUS		mandatory
    DESCRIPTION
				"The value of a single sensor reading, or one half of a 64-bit reading,
				in integer format, not translated to human-readable form. See
				POEXSensorDeviceReadingU32Value for further explanation."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 10 }

POEXSensorInfoBySensorIDSensorDeviceReadingValue2 OBJECT-TYPE
    SYNTAX		POEXSensorDeviceReadingU32Value
    ACCESS		read-only
    STATUS		mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
		INDEX   { POEXSensorID }
  	::= {POEXSensorInfoBySensorIDEntry 11 }

POEXSensorInfoBySensorIDSensorDeviceReadingValue3 OBJECT-TYPE
		SYNTAX		POEXSensorDeviceReadingU32Value
	  ACCESS		read-only
	  STATUS		mandatory
		DESCRIPTION
				"The value of a single sensor reading, or one half of a 64-bit reading,
				in integer format, not translated to human-readable form. See
				POEXSensorDeviceReadingU32Value for further explanation."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 12 }

POEXSensorInfoBySensorIDSensorDeviceReadingValue4 OBJECT-TYPE
    SYNTAX		POEXSensorDeviceReadingU32Value
    ACCESS		read-only
    STATUS		mandatory
    DESCRIPTION
				"The value of a single sensor reading, or one half of a 64-bit reading,
	 			in integer format, not translated to human-readable form. See
	 			POEXSensorDeviceReadingU32Value for further explanation."
		INDEX   { POEXSensorID }
	  ::= {POEXSensorInfoBySensorIDEntry 13 }

POEXSensorInfoBySensorIDSensorDeviceReadingValue5 OBJECT-TYPE
    SYNTAX		POEXSensorDeviceReadingU32Value
    ACCESS		read-only
    STATUS		mandatory
    DESCRIPTION
		 		"The value of a single sensor reading, or one half of a 64-bit reading,
				in integer format, not translated to human-readable form. See
				POEXSensorDeviceReadingU32Value for further explanation."
		INDEX   { POEXSensorID }
 		::= {POEXSensorInfoBySensorIDEntry 14 }

POEXSensorInfoBySensorIDSensorDeviceReadingValue6 OBJECT-TYPE
    SYNTAX		POEXSensorDeviceReadingU32Value
    ACCESS		read-only
    STATUS		mandatory
    DESCRIPTION
		  	"The value of a single sensor reading, or one half of a 64-bit reading,
		 		in integer format, not translated to human-readable form. See
		 		POEXSensorDeviceReadingU32Value for further explanation."
		INDEX   { POEXSensorID }
		::= {POEXSensorInfoBySensorIDEntry 15 }

POEXSensorInfoBySensorIDSensorDeviceReadingValue7 OBJECT-TYPE
    SYNTAX		POEXSensorDeviceReadingU32Value
    ACCESS		read-only
    STATUS		mandatory
    DESCRIPTION
			 	"The value of a single sensor reading, or one half of a 64-bit reading,
				in integer format, not translated to human-readable form. See
				POEXSensorDeviceReadingU32Value for further explanation."
		INDEX   { POEXSensorID }
		::= {POEXSensorInfoBySensorIDEntry 16 }

POEXSensorInfoBySensorIDSensorDeviceReadingValue8 OBJECT-TYPE
    SYNTAX		POEXSensorDeviceReadingU32Value
    ACCESS		read-only
    STATUS		mandatory
    DESCRIPTION
				"The value of a single sensor reading, or one half of a 64-bit reading,
				in integer format, not translated to human-readable form. See
				POEXSensorDeviceReadingU32Value for further explanation."
		INDEX   { POEXSensorID }
		::= {POEXSensorInfoBySensorIDEntry 17 }

 --
 -- Sensor-specific section, untranslated legacy format, by registration order
 --

POEXSensorInfoBySensorRegisOrderTable OBJECT-TYPE
		SYNTAX				SEQUENCE OF POEXSensorInfoBySensorRegisOrderSensorEntry
		ACCESS    		not-accessible
		STATUS        mandatory
		DESCRIPTION
				"The (conceptual) table containing an untranslated numeric format,
				addressed by sensor registration order starting at 1 and ascending by
				one, in a legacy integer format. This is provided for users who need a
 				precise match of the format and order of the older EGW1 platform.
 				The gateway will report the most current information received from
 				sensors, according to their programmed reporting period or heartbeat.
				A more convenient format to new users is available under
				the POEXSensorInfoTranslatedFormat. If queried, this
				OID will return the number of rows in the table, which is the number
				of sensors registered to this gateway."
		::= { POEX 4 }

POEXSensorInfoBySensorRegisOrderEntry OBJECT-TYPE
		SYNTAX				POEXSensorInfoBySensorRegisOrderEntry
		ACCESS    		not-accessible
		STATUS        mandatory
		DESCRIPTION
				"An entry (conceptual row) in the untranslated by-registration-order
 				table containing the latest sensor state for a single sensor."
		INDEX   { POEXSensorInfoBySensorRegisOrderSensDevID }
		::= { POEXSensorInfoBySensorRegisOrderTable 1 }

POEXSensorInfoBySensorRegisOrderEntry ::= SEQUENCE {
		POEXSensorInfoBySensorRegisOrderSensorDeviceID Unsigned32,
		POEXSensorInfoBySensorRegisOrderSensorDeviceWDIndexNo INTEGER,
		POEXSensorInfoBySensorRegisOrderSensorDeviceTypeNo INTEGER,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingAge Unsigned32,
		POEXSensorInfoBySensorRegisOrderSensorDeviceActive INTEGER,
		POEXSensorInfoBySensorRegisOrderSensorDeviceAlarming INTEGER,
		POEXSensorInfoBySensorRegisOrderSensorDeviceVoltage INTEGER,
		POEXSensorInfoBySensorRegisOrderSensorDeviceRFStrength INTEGER,
		POEXSensorInfoBySensorRegisOrderSensorDeviceRptUT DisplayString,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue1 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue2 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue3 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue4 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue5 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue6 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue7 POEXSensorDeviceReadingU32Value,
		POEXSensorInfoBySensorRegisOrderSensorDeviceReadingValue8 POEXSensorDeviceReadingU32Value
}

POEXSensorInfoBySensorRegisOrderSensDevID OBJECT-TYPE
    SYNTAX        Unsigned32
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The serial number identifier of the sensor device assigned and
  			programmed by the manufacturer. This will ordinarily be printed
  			on a label on the housing of the device."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 1 }

POEXSensorInfoBySensorRegisOrderSensDevWDIndexNo OBJECT-TYPE
    SYNTAX        INTEGER(0..255)
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The index number of the sensor in the gateway's sensor registration
  			table. This is the number used in referencing the sensor in the
  			POEXSensorInfoBySensorRegisOrder hierarchy."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 2 }

POEXSensorInfoBySensorRegisOrderSensDevTypeNo OBJECT-TYPE
    SYNTAX        INTEGER(1..65535)
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The manufacturer's type number that identifies the kind of sensor."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 3 }

POEXSensorInfoBySensorRegisOrderSensDevReadingAge OBJECT-TYPE
    SYNTAX        Unsigned32
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The age of the sensor report received most recently from a sensor.
  			That time is reported as the number of seconds between the time of
  			the sensor report and the time this information is requested."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 4 }

POEXSensorInfoBySensorRegisOrderSensDevActive OBJECT-TYPE
    SYNTAX        INTEGER(0..1)
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"Either 1 (active) or 0 (inactive). A sensor will be reported active
 				if it has recently communicated with the gateway since the last
  			reboot. If a sensor device does not show active, it is likely because
  			(1) the sensor lacks a power source, (2) the sensor is not in
  			proximity to the gateway, or (3) the gateway has recently been
  			powered on, and the sensor hasn't yet communicated."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 5 }

POEXSensorInfoBySensorRegisOrderSensDevAlarming OBJECT-TYPE
		SYNTAX        	INTEGER(0..1)
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"Either 1 (alarming) or 0 (not alarming)'. A device will report an
 				alarm if it is programmed with a threshold found to be exceeded.
 				Examples: a temperature sensor for a refrigeration unit can be
 				programmed to alarm if the measured temperature rises above a
 				threshold, and a door sensor might alarm if a security door is opened."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 6 }

POEXSensorInfoBySensorRegisOrderSensDevVoltage OBJECT-TYPE
		SYNTAX        	INTEGER(0..255)
    ACCESS    			read-only
    STATUS       	mandatory
    DESCRIPTION
 				"A value representing the voltage of the supply powering a sensor
 				device. Ordinarily this will report the voltage at the battery
 				terminals of a sensor. It is provided mainly so batteries can be
 				changed when depleted. The formula for calculating the voltage from
 				this number is: voltage=(150 + v) / 10.0."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 7 }

POEXSensorInfoBySensorRegisOrderSensDevRFStrength OBJECT-TYPE
    SYNTAX        INTEGER(-128..127)
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The signal strength, in percent, of the radio link between the gateway
  			and the particular sensor, as measured at the time of the most recent
  			sensor report."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 8 }

POEXSensorInfoBySensorRegisOrderSensDevRptUT OBJECT-TYPE
    SYNTAX        DisplayString
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The untranslated data block received from a sensor, in hexadecimal
  			format. This may be used where a translating function isn't yet
  			present, and for development purposes. Most users should use the
				translated values delivered in the format of
				POEXSensorDeviceReadingValuesAll."
		INDEX   { POEXSensorRegistrationIndex }
  	::= {POEXSensorInfoBySensorRegisOrderEntry 9 }

POEXSensorInfoBySensorRegisOrderSensDevReadingVl1 OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingU32Value
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
  	::= {POEXSensorInfoBySensorRegisOrderEntry 10 }

POEXSensorInfoBySensorRegisOrderSensDevReadingVl2 OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingU32Value
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
  	::= {POEXSensorInfoBySensorRegisOrderEntry 11 }

POEXSensorInfoBySensorRegisOrderSensDevReadingVl3 OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingU32Value
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
  	::= {POEXSensorInfoBySensorRegisOrderEntry 12 }

POEXSensorInfoBySensorRegisOrderSensDevReadingVl4 OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingU32Value
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
  	::= {POEXSensorInfoBySensorRegisOrderEntry 13 }

POEXSensorInfoBySensorRegisOrderSensDevReadingVl5 OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingU32Value
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
  	::= {POEXSensorInfoBySensorRegisOrderEntry 14 }

POEXSensorInfoBySensorRegisOrderSensDevReadingVl6 OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingU32Value
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
  	::= {POEXSensorInfoBySensorRegisOrderEntry 15 }

POEXSensorInfoBySensorRegisOrderSensDevReadingVl7 OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingU32Value
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
  	::= {POEXSensorInfoBySensorRegisOrderEntry 16 }

POEXSensorInfoBySensorRegisOrderSensDevReadingVl8 OBJECT-TYPE
    SYNTAX        POEXSensorDeviceReadingU32Value
    ACCESS    		read-only
    STATUS        mandatory
    DESCRIPTION
  			"The value of a single sensor reading, or one half of a 64-bit reading,
 				in integer format, not translated to human-readable form. See
 				POEXSensorDeviceReadingU32Value for further explanation."
  	::= {POEXSensorInfoBySensorRegisOrderEntry 17 }

--
-- Traps
--

--Map of types used in traps to those used in requests
--	POEX-Trap-DevIDReported ::= POEX-GatewayID
--	POEX-Trap-AllValuesReported ::=
-- 		CHOICE {
--							POEX-trap-values-translatable POEX-SensorDeviceReadingValuesAll,
--							POEX-trap-values-unknown POEX-SensorDeviceReadingUntranslated
--					 }
--	POEX-Trap-AllUnitsReported ::= POEX-SensorDeviceReadingUnitsAll
--	POEX-Trap-AgeReported ::= POEX-SensorDeviceReadingUnitsAll
--	POEX-Trap-AlarmingReported ::= POEX-SensorDeviceReadingUnitsAll

POEXTrapDevIDReported ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The serial number identifier of the sensor device assigned and
				programmed by the manufacturer. This will ordinarily be printed
				on a label on the housing of the device. POEXTrapDevIDReported
				is the same as POEXSensorID."
		SYNTAX				Unsigned32(1..2147483631)

POEXTrapAllValuesReported ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"This will make one of two reports. For the case the sensor type is
				known to the gateway, this will be all of the datums for the most
 				recent reading of the sensor device, separated by commas, in textual
 				format, using the POEXSensorDeviceReadingValuesAll format.
				Where the sensor type is not known to the gateway, this will be
				the untranslated data block received from a sensor, in hexadecimal
				format. This POEXTrapAllValuesReported is the same as either
				POEXSensorDeviceReadingValuesAll or
 				POEXSensorDeviceReadingUntranslated."
		SYNTAX				OCTET STRING

POEXTrapAllUnitsReported ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"All of the units corresponding to the datums for the most recent
				reading of the sensor device, separated by commas, in textual
				format. For example, for a sensor reporting temperature and
				humidity this might read 'degrees C, %RH'.
				POEXTrapAllUnitsReported is the same as
 				POEXSensorDeviceReadingUnitsAll."
		SYNTAX				OCTET STRING

POEXTrapAgeReported ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"The age of the sensor report received most recently from a sensor.
				That time is reported as the number of seconds between the time of
				the sensor report and the time this information is requested.
				POEXTrapAgeReported is the same as
				POEXSensorDeviceReadingAge."
		SYNTAX				OCTET STRING

POEXTrapAlarmingReported ::= TEXTUAL-CONVENTION
		STATUS        mandatory
		DESCRIPTION
				"Either 'Alarming' or 'Not alarming'. A device will report an alarm
				if it is programmed with a threshold found to be exceeded. Examples:
				a temperature sensor for a refrigeration unit can be programmed to
				alarm if the measured temperature rises above a threshold, and
				a door sensor might alarm if a security door is opened.
				POEXTrapAlarmingReported is the same as
				POEXSensorDeviceReadingAlarming."
		SYNTAX				OCTET STRING

POEXNewSensorTraffic TRAP-TYPE
	ENTERPRISE POEX
	VARIABLES {
							POEXSensorInfoTranslatedFormatSensorDeviceID, POEXTrapDevIDReported,
							POEXSensorInfoTranslatedFormatSensorDeviceReadingValuesAll, POEXTrapAllValuesReported,
							POEXSensorInfoTranslatedFormatSensorDeviceReadingUnitsAll, POEXTrapAllUnitsReported,
							POEXSensorInfoTranslatedFormatSensorDeviceReadingAge, POEXTrapAgeReported,
							POEXSensorInfoTranslatedFormatSensorDeviceAlarming, POEXTrapAlarmingReported
						}
	DESCRIPTION
			"This trap, when enabled, will generate a report corresponding to new
 			data from any registered sensor as it is received. Included with the
 			trap message are the sensor ID, all values the sensor reports, units for
 			all those values, the age, and whether the sensor is alarming."
	::= 1

POEXDeviceAlarming TRAP-TYPE
	ENTERPRISE POEX
	VARIABLES {
							POEXSensorInfoTranslatedFormatSensorDeviceID, POEXTrapDevIDReported,
							POEXSensorInfoTranslatedFormatSensorDeviceReadingValuesAll, POEXTrapAllValuesReported,
							POEXSensorInfoTranslatedFormatSensorDeviceReadingUnitsAll, POEXTrapAllUnitsReported,
							POEXSensorInfoTranslatedFormatSensorDeviceReadingAge, POEXTrapAgeReported,
							POEXSensorInfoTranslatedFormatSensorDeviceAlarming, POEXTrapAlarmingReported
						}
	DESCRIPTION
			"This trap, when enabled, will generate a report corresponding to new
 			data from any registered sensor as it is received, but only if that
			sensor is alarming and the POEXNewSensorTraffic trap is disabled.
			(That trap will generate the same message, rendering this trap redundant.)
			Included with the trap message are the sensor ID, all values the sensor
 			reports, units for all those values, the age, and whether the sensor
 			is alarming."
	::= 2

END